Scott-T Connection of
Transformer:
Transforming 3 Phase to 2 Phase:
§ There are two main reasons for the need to
transform from three phases to two phases,
1.
To give a supply to an existing two phase system from a three
phase supply.
2.
To supply two phase furnace transformers from a three phase
source.
§ Two-phase systems can have 3-wire, 4-wire, or
5-wire circuits. It is needed to be considering that a two-phase system is not
2/3 of a three-phase system. Balanced three-wire, two-phase circuits have two
phase wires, both carrying approximately the same amount of current, with a
neutral wire carrying 1.414 times the currents in the phase wires. The
phase-to-neutral voltages are 90° out of phase with each other.
§ Two phase 4-wire circuits are essentially just
two ungrounded single-phase circuits that are electrically 90° out of phase
with each other. Two phase 5-wire circuits have four phase wires plus a
neutral; the four phase wires are 90° out of phase with each other.

§ The easiest way to transform three-phase
voltages into two-phase voltages is with two conventional single-phase
transformers. The first transformer is connected phase-to-neutral on the
primary (three-phase) side and the second transformer is connected between the
other two phases on the primary side.
§ The secondary windings of the two transformers
are then connected to the two-phase circuit. The phase-to-neutral primary
voltage is 90° out of phase with the phase-to-phase primary voltage, producing
a two-phase voltage across the secondary windings. This simple connection,
called the T connection, is shown in Figure
§ The main advantage of the T connection is that
it uses transformers with standard primary and secondary voltages. The
disadvantage of the T connection is that a balanced two-phase load still
produces unbalanced three-phase currents; i.e., the phase currents in the
three-phase system do not have equal magnitudes, their phase angles are not
120° apart, and there is a considerable amount of neutral current that must be
returned to the source.
The Scott Connection of
Transformer:
§ A Scott-T transformer (also called a Scott
connection) is a type of circuit used to derive two-phase power from a
three-phase source or vice-versa. The Scott connection evenly distributes a
balanced load between the phases of the source.
§ Scott T Transformers require a three phase power
input and provide two equal single phase outputs called Main and Teaser. The
MAIN and Teaser outputs are 90 degrees out of phase. The MAIN and the Teaser
outputs must not be connected in parallel or in series as it creates a vector
current imbalance on the primary side.
§ MAIN and Teaser outputs are on separate cores.
An external jumper is also required to connect the primary side of the MAIN and
Teaser sections.
§ Scott T Transformer is built with two single
phase transformers of equal power rating. The MAIN and Teaser sections can be
enclosed in a floor mount enclosure with MAIN on the bottom and Teaser on top
with a connecting jumper cable. They can also be placed side by side in
separate enclosures.
§ Assuming the desired voltage is the same on the
two and three phase sides, the Scott-T transformer connection consists of a
center-tapped 1:1 ratio main transformer, T1, and an 86.6% (0.5√3) ratio teaser
transformer, T2. The center-tapped side of T1 is connected between two of the
phases on the three-phase side. Its center tap then connects to one end of the
lower turn count side of T2, the other end connects to the remaining phase. The
other side of the transformers then connects directly to the two pairs of a
two-phase four-wire system.
§ The Scott-T transformer connection may be also
used in a back to back T to T arrangement for a three-phase to 3 phase
connection. This is a cost saving in the smaller kVA transformers due to the 2
coil T connected to a secondary 2 coil T in-lieu of the traditional three-coil
primary to three-coil secondary transformer. In this arrangement the Neutral
tap is part way up on the secondary teaser transformer . The voltage stability
of this T to T arrangement as compared to the traditional 3 coil primary to three-coil
secondary transformer is questioned



No comments:
Post a Comment